Low Flow Rate Ultrasonic Water Meter Custom

KeytureMeter
Ultrasonic · Low Flow · R800

Low Flow Rate Ultrasonic Water Meter

An ultrasonic meter built to measure the smallest flows — R800 range ratio, minimum flow of 2 – 8 L/h, zero-stable electronics and 24-hour continuous-flow leak alarms.

  • R800 range ratio: Q1 of only 2 – 8 L/h on DN15 – DN25
  • Folded acoustic path and picosecond timing resolve flows of a few mm/s
  • Zero-cutoff and low-flow averaging prevent phantom volume
  • 24-hour continuous-flow leak alarm; Class 1; battery up to 12 years

R800 · picosecond timing · zero-stable · leak alarm

Product Introduction

What Is a Low Flow Rate Ultrasonic Water Meter?

A low flow rate ultrasonic water meter is an ultrasonic meter optimised for the opposite end of the range from a bulk meter. Instead of maximising capacity, it is designed to measure the smallest flows reliably: the thin trickle from a leaking toilet valve, the slow drip from a worn tap washer, the creeping flow of a drip irrigation line or the continuous few litres per hour that signal a pipe leak behind a wall. For a household meter, flows of 2 to 10 litres per hour are the most economically valuable flows to detect — they run for days or weeks unnoticed, they waste more water than any single large event and they are invisible to all but the most sensitive meters. The meter’s defining specification is therefore its range ratio, R800, and with it a minimum flow Q1 of only 2 to 8 litres per hour depending on size.

Measuring such small flows with sound is a challenge of resolution. At 2 litres per hour in a 15 mm tube, the water moves at about 3 millimetres per second. The difference between the upstream and downstream transit times, over a path of 10 cm, is only a few hundred picoseconds — a fraction of one billionth of a second. To resolve it, the meter uses time-to-digital converters with picosecond resolution, averages thousands of pulse pairs for each reading and compensates the temperature of the water continuously, since a change of one degree changes the speed of sound enough to swamp the signal. Zero stability is as important as sensitivity: with no flow, the meter must read zero, not a slow drift that would be billed as water.

The design therefore adds three features. A longer, folded acoustic path increases the time difference at a given velocity. A low-flow measurement mode averages over several seconds and applies a zero-cutoff, so that noise does not accumulate as phantom volume. And a leak-detection function tracks the minimum flow over a rolling window — if flow never falls to zero for 24 hours, the meter raises an alarm. Supplied in DN15 to DN25 with Q3 values of 1.6 to 6.3 m³/h, R800, Class 1 accuracy under ISO 4064 / OIML R49, battery life of up to 12 years and M-Bus or wireless options, the low flow rate ultrasonic water meter is built for the places where small flows matter most.

Key takeaway: Big leaks get noticed. Small ones run for months. A low flow rate ultrasonic meter is designed to see the slow trickle and prove it with a minimum flow of a few litres per hour.

Design Advantages

Why Choose a Low Flow Rate Ultrasonic Meter

Six design features that matter when the flows you care about are measured in litres per hour.

01

R800 Range Ratio

Minimum flow is one eight-hundredth of permanent flow. A DN15 meter with Q3 of 1.6 m³/h measures accurately down to 2 litres per hour — a flow that most mechanical meters do not even register.

02

Folded Acoustic Path

A reflector folds the sound path so it crosses the flow more than once. Longer path length gives a larger time difference at the same velocity, improving signal at very low flow.

03

Picosecond Timing and Averaging

Time-to-digital converters resolve hundreds of picoseconds, and averaging over thousands of pulse pairs reduces noise further. Flow of a few mm/s becomes a stable reading.

04

Zero Stability

With no flow, the meter must read zero. A zero-cutoff, temperature-compensated drift correction and a tight zero-offset specification stop noise from becoming phantom volume on the bill.

05

Continuous-Flow Leak Alarm

If flow never drops to zero over a 24-hour window, the meter flags a probable leak. Customers and utilities can fix toilets and pipe leaks long before they show on a monthly bill.

06

Small Q3 Choices

Q3 of 1.6 and 2.5 m³/h in DN15 give lower minimum flow than the usual 2.5 or 4 m³/h options. A smaller Q3 suits households that never need high flow and gains sensitivity.

Technical Data

Specifications

Standard configuration below. Q3, reporting interval and communication can be adapted to your leak detection and billing requirements.

General Specifications
ParameterSpecification
StandardISO 4064 / OIML R49
Meter typeTransit-time ultrasonic, folded dual-path, static, low flow optimised
Nominal diameterDN15 – DN25 (1/2" – 1")
Permanent flow Q31.6 / 2.5 / 4 / 6.3 m³/h
Accuracy classClass 1, R800 standard
Minimum flow Q12.0 L/h (Q3 1.6) to 7.9 L/h (Q3 6.3)
Starting flow≤ 1 L/h (DN15, Q3 1.6)
Zero stabilityZero offset ≤ ±0.2 L/h after temperature compensation
Timing resolutionPicosecond-class time-to-digital converter, multi-pulse averaging
Low-flow averaging window4 – 8 s, selectable
Zero-cutoffProgrammable, default 0.5 L/h
Leak alarmContinuous flow > 24 h; configurable window and threshold
Water temperature0.1 °C – 50 °C (cold water)
Working pressureMAP 16 bar
Pressure loss≤ 0.025 MPa at Q3
Power supply3.6 V lithium battery, up to 12 years
CommunicationM-Bus, LoRaWAN, NB-IoT, pulse (optional)
ProtectionIP68
Size Selection

Flow Data by Size

Q4 is the overload flow, Q3 the permanent flow, Q2 the transitional flow and Q1 the minimum flow, all expressed in m³/h.

Metrological Data — R800
Nominal Diameter and Q3Q4 OverloadQ3 PermanentQ2 TransitionalQ1 MinimumRange RatioQ1 in Litres per Hour
DN15 (1/2") — Q3 1.621.60.00320.002R8002.0 L/h
DN15 (1/2") — Q3 2.53.1252.50.0050.003125R8003.1 L/h
DN20 (3/4") — Q3 4540.0080.005R8005.0 L/h
DN25 (1") — Q3 6.37.8756.30.01260.007875R8007.9 L/h

Values shown for R800. Q3 of 1.6 m³/h suits households that never need high flow; larger Q3 values suit properties with higher peak demand. Tell us the property type and peak flow and we will confirm the correct Q3 so the meter gains sensitivity without risking overload.

Certification

Standards & Compliance

Measuring very small flows demands careful verification at the bottom of the range, with test rigs that have the resolution to prove it.

ISO 4064 / OIML R49

Class 1 limits and test points for electronic water meters with high R values, including verification at Q1 and Q2 where the flow is only a few litres per hour.

Low-Flow Test Rig Uncertainty

Rigs used at Q1 operate with controlled temperature, degassed water, closed collection and balances with gram-class resolution to resolve a few litres per hour.

Zero-Flow Stability Test

The meter is tested for zero offset over temperature and time, with the pipe full and stationary, to confirm no phantom volume accumulates.

Temperature Compensation Validation

Calibration at several water temperatures verifies that speed-of-sound compensation keeps low-flow readings stable within the specified range.

EMC & Immunity

Tests for ESD, EFT, surge and radiated immunity confirm that picosecond-level timing and low-flow readings are not disturbed by interference.

Leak Alarm Verification

Alarm logic is verified with simulated continuous flows of 1, 2 and 5 L/h over 24 hours, confirming that alarms trigger and reset as specified.

Honors and Certificates

Every certificate has witnessed our speciality.

Explore More

Get in Touch With Us

Send Message
How It Works

Technology & Design

Two techniques define this meter: how a few millimetres per second becomes a measurable signal, and how zero is kept at zero.

Resolving Millimetres per Second

The transit-time difference Δt between upstream and downstream pulses is proportional to the product of path length and flow velocity, divided by the square of the speed of sound. For a 10 cm path, a speed of sound near 1,480 m/s and a velocity of 3 mm/s — roughly 2 litres per hour in a 15 mm tube — Δt is about 0.27 nanoseconds. A conventional low-cost timer cannot resolve it directly.

Three techniques make it measurable. A reflector folds the acoustic path so the sound crosses the flow twice, doubling Δt. A time-to-digital converter with picosecond resolution measures each transit time to a few tens of picoseconds. And the processor averages thousands of pulse pairs in a few seconds, reducing random noise by the square root of the number of pairs. The averaged result resolves hundreds of picoseconds with good repeatability.

  • Δt ≈ 0.27 ns at 2 L/h on DN15 with a 10 cm path
  • Folded reflector path doubles the time difference
  • Picosecond time-to-digital converter
  • Averaging thousands of pulse pairs reduces noise
0.27 ns Time difference at
2 L/h on DN15
R800 Standard range ratio
≤ 1 L/h Starting flow
DN15, Q3 1.6

Zero Stability, Cut-Off and Leak Detection

Because sensitivity is so high, noise and drift are the enemies. The speed of sound changes by about 0.2 percent per degree, and a tiny difference in electronic delays between upstream and downstream channels appears as a flow offset. The meter measures water temperature continuously, applies a stored compensation and re-learns its zero offset during periods of no flow, when the pipe is full but stationary.

A zero-cutoff sets a threshold below which readings are treated as zero, so noise does not accumulate. The threshold is chosen below Q1 and well below any real leak. The same flow history feeds the leak detector: the meter keeps a rolling record of the minimum flow in each hour, and if the minimum stays above the cutoff for 24 hours — meaning there was never a period of no flow — a leak alarm is raised. The alarm threshold and window can be changed remotely.

  • Temperature-compensated speed of sound
  • Zero offset re-learned during no-flow periods
  • Programmable zero-cutoff below Q1
  • 24-hour continuous-flow leak alarm
  • Alarm window and threshold configurable remotely
±0.2 L/h Zero offset after
compensation
24 h Continuous-flow
leak alarm window
12 yrs Battery life at
daily uplink
Performance Data

Head Loss, Accuracy & Dimensions

Measured performance data for the low flow rate ultrasonic water meter. Use these charts to confirm pressure loss, low-flow accuracy and installation dimensions before specifying.

0 0.005 0.010 0.015 0.020 0.025 1.6 2.5 4 5 6.3 Head loss MPa Flow(m³/h) 15mm Q3 1.6 15mm Q3 2.5 20mm 25mm 2. Head Loss Curve

Figure 1 — Head loss curve (MPa vs. flow m³/h)

Head Loss Curve

The chart shows pressure loss for the four standard configurations. Because the tube is smooth and unobstructed, loss at Q3 stays at or below 0.025 MPa. A smaller Q3 on the same DN15 body gives a slightly narrower measuring section and a little more loss at its higher end, though the flows are lower.

  • Pressure loss at Q3 ≤ 0.025 MPa
  • Full-bore tube, no obstruction
  • Check pressure only for small Q3 variants at high flow
+3 +1 0 -1 -3 Q1 Q2 Q3 Q4 ± 3 % ± 1 % Error% Flow 3. Accuracy Error Curve

Figure 2 — Accuracy error curve (Class 1, R800, Q1–Q4)

Accuracy Error Curve

At Q1 — only 2 L/h on a DN15 — the error is within ±1.5%, half of the ±3% Class 1 limit. From Q2 upward, the curve is flat within ±0.5%. The result confirms that the very high range ratio does not compromise accuracy at ordinary flows.

  • ±3% lower zone, ±1% upper zone (Class 1)
  • Error within ±1.5% at Q1
  • Flat within ±0.5% from Q2 upward
3 L H B D 4. Installation Dimension

Figure 3 — Installation dimensions (L × H × B × D)

Installation Dimensions by Size
SizeL (mm)H (mm)B (mm)D (thread)
DN151659578G3/4"
DN2019010080G1"
DN2526011292G1¼"

Dimensions are for reference. Confirm exact values with our engineering team before installation design.

Design Comparison

Low Flow Ultrasonic vs. Other Low-Flow Meters

Several meter types can measure small flows. This table compares the low flow ultrasonic meter with the main alternatives.

Comparison of Low-Flow Measuring Technologies
Design FeatureLow Flow Ultrasonic (R800)Rotary Piston (R400)Multi Jet (R100)
Minimum flow Q1, DN15, Q3 2.5About 3 L/hAbout 6 L/hAbout 25 L/h
Starting flow≤ 1 L/h≤ 2 L/hAbout 8 L/h
Wear over lifeNonePiston and chamber wearImpeller and bearing wear
Sensitivity to dirty waterLowHigh — needs fine strainerModerate
Leak alarm built inYes — 24 h continuous flowNoNo
Power requirementBatteryNoneNone
Zero-flow behaviourMust be kept zero by designNaturally zeroNaturally zero
Best applicationLeak detection and revenue capturePremium mechanicalGeneral residential

This comparison is indicative. Actual performance depends on water quality, installation and the specific product configuration. Contact our engineers for application-specific guidance.

Premium quality

since 2002

Coming From China, Marketing To The World

Keyture Meter is located in Picturesque Jiangbei Investment Park, NINGBO, CHINA. It is a comprehensive high-tech China Low Flow Rate Ultrasonic Water Meter Manufacturers and Custom Low Flow Rate Ultrasonic Water Meter Factory that integrates scientific research & development, production, sales, and service. Established in 2002 as a manufacturer and exporter of water meters for more than 22 years. The factory covers an area of 40 acres (30,000 square meters), 200 staff, 100+ types of products, product capacity of 5 million per year. Its product range covers single jet, multi-jet, volumetric piston type, Woltman type, IC card intelligent water meter, remote control water meter, optoelectrical reading direct remote control water meter...

  • 0million

    Yearly production capacity

  • 0+㎡

    Production Area

  • 0People

    Works and inspectors

  • 0+ years

    Production experience

What Sets Us Apart

Excellent product with exquisite craftsmanship

Customization

We have a strong R&D team, and we can develop and produce products according to the drawings or samples the customers offered.

Cost

We are a professional manufacturer and also have our own processing machinery. So we can offer good prices and good products directly.

Quality

We have our own testing lab and advanced and complete inspection equipment, which can ensure the quality of the products.

Service

We focus on developing high-quality products for top-end markets. Our products are in line with international standards, and are mainly exported to Europe, America, Africa, Asia and other destinations around the world.

Capacity

Our annual production capacity is over 5 million units. We can meet the needs of different customers with different purchase quantities.

Shipment

We are about 35 kilometers away from Ningbo Port. It is very convenient and efficient to ship goods to any other countries.

Solution

Complete Metering Solutions

From mechanical meters to smart AMR/AMI systems — we provide end-to-end water metering solutions tailored to your project.

Complete water metering solution by Keyture Meter
Where It Works

Applications

Where small continuous flows are the problem to solve.

Leak Detection ProgrammesHouseholds and buildings where hidden leaks cause large losses.
Vacation & Second HomesProperties left empty for weeks where a trickle can become a flood.
Water-Saving CampaignsUtilities giving customers alerts for running cisterns and dripping taps.
Drip IrrigationGardens and farms with long, slow flows to be measured accurately.
Insurance & Property ManagementPortfolios where early leak alerts reduce claims.
Premium Residential BillingCustomers expecting every litre to be measured fairly.
Field Guidance

Installation & Maintenance

Installation Best Practices

Install the meter in the direction of the flow arrow and make sure the pipe is full at all times. Air bubbles disrupt the ultrasonic signal at very low velocity, so avoid installing at the highest point of a pipe and vent any air before commissioning. A vertical upward flow is a good position for low-flow meters because bubbles rise out of the tube.

Choose Q3 to match the property. A household with a DN15 supply and a maximum demand of 1.5 m³/h can use Q3 of 1.6, giving Q1 of 2 L/h. A larger property that sometimes draws 3 m³/h should use Q3 of 2.5 or 4 to avoid overload.

After installation, make sure all taps are closed and read the meter. It should read zero flow. Check the leak alarm status after 24 hours. If the alarm triggers, look for continuous leaks such as toilet cisterns or irrigation controllers before assuming a meter fault.

Full pipeNo air at low velocity
Q3Match to peak demand
Zero checkWith all taps closed

Maintenance & Service Life

The low flow ultrasonic meter has no moving parts and needs no routine maintenance. The platform reports zero-offset and battery status, and the meter flags any signal quality problem, such as air or transducer degradation, before accuracy is affected.

If leak alarms are frequent, check whether the cause is a real leak or a configuration problem — for example, a swimming pool automatic top-up or a garden controller that runs continuously at a low rate. The alarm window and threshold can be adjusted remotely to match the property.

Typical service life is 12 years, limited by the battery. The measuring tube does not wear, so its accuracy remains stable, and many utilities extend verification after sample testing.

ReportZero offset and signal
quality on platform
TuneAlarm window for
pools and irrigation
12 yrsTypical service life
limited by battery
Questions

Frequently Asked Questions

What is the minimum flow of the meter?

It depends on size and Q3. For a DN15 with Q3 of 1.6 m³/h and R800, Q1 is 2 litres per hour. For Q3 2.5 it is about 3 L/h, and for DN25 with Q3 6.3 it is about 8 L/h.

Why does a lower Q3 improve low-flow performance?

The range ratio R is Q3 divided by Q1. With the same R800, a lower Q3 gives a lower Q1. A household that never needs more than 1.5 m³/h can use Q3 1.6 and measure down to 2 L/h.

How does the meter measure such tiny flows?

It uses a folded acoustic path, picosecond timing electronics and averaging over thousands of pulse pairs. These techniques turn a time difference of a fraction of a nanosecond into a stable reading.

What is zero stability and why does it matter?

Zero stability is the meter’s ability to read zero when there is no flow. If the zero drifts, the meter would count phantom volume that appears on the bill. The meter compensates for temperature, re-learns its zero offset during no-flow periods and applies a cutoff.

How does the leak alarm work?

The meter tracks the minimum flow in each hour. If the minimum stays above the cutoff for 24 hours, meaning there was no period of zero flow, the meter flags a probable leak. The window and threshold can be changed by downlink.

Can false alarms occur?

Yes, if a legitimate device runs continuously, such as a pool top-up, an aquarium or an irrigation controller. The window or threshold can be adjusted for such properties.

Is the meter affected by air bubbles?

At very low velocity, air bubbles can interrupt the ultrasonic signal. The meter flags air and resumes measurement when full flow returns. Install it in a full pipe and bleed air at commissioning.

What accuracy class does it have?

Class 1 under ISO 4064 / OIML R49 with R800 range ratio. At Q1 the error is within ±3%, and above Q2 within ±1%, with typical results far better.

What power does it use?

A 3.6 V lithium battery with a typical life of up to 12 years at daily reporting. The low-flow mode averages over several seconds, which uses slightly more power than a standard ultrasonic meter.

What communication options are available?

M-Bus, LoRaWAN, NB-IoT and pulse output. Leak alarms can be sent immediately by wireless versions, and M-Bus versions provide the alarm status in the data telegram.

Can the meter be used for hot water?

The standard version is for cold water. A hot water low-flow model is possible, but the transducers and electronics must be selected for temperature. Please contact us with your requirements.

Is the meter suitable for high-demand properties?

Choose a larger Q3. For properties with peak demand above the Q3 of the meter, a larger meter or a combination setup should be used so that overload does not occur.

Tell us about your smallest flows

Send us the property type, peak demand and the leak size you want to detect. Our engineers will recommend the right Q3 and low flow ultrasonic configuration, with price and lead time.

Request a Quote